Leave Your Message

LMCT1 Series Automatic Transfer Switch Equipment ATS 2000G

Model Name: LMCT1-2000G

Rated Voltage: AC380V,AC400V,AC415V

Rated Current: 800A,1000A,1250A,1600A,2000A

Pole: 3P,4P

Product Category: PC Class

Rated Insulation Voltage:AC1000V

Rated Control Power Current:16A

Rated lmpulse Withstand Voltage:12kV

Working Position:I-closed,I-closed,0-position

Limited Short-Circuit Current:120kA(frontfuseprotection)

Usage Category:AC-33B

ElectricalLife:3000 times

MechanicalLife:7000 times

Certification: CCC

Standard: GB/T14048.11
           IEC60947-6-1

Email: sale@lvma-ele.com

rEAD more
9

This automatic transfer switch equipment is a specialty product developed byour company,complying with GB/T14048.11 standards,as wellas the "Code forFire Protection Design of Tall Buildings"and the "Emergency Lighting DesignGuide."Components and parts have undergone rigorous aging screening,andfinished products pass confirmation testing before leaving the factory,ensuring product reliability and safety.
It is suitable for power distribution systems with a rated working voltage ofAC400V.In cases of power supply faults such as loss phase,overvoltage,andunder-voltage,the transfer switch can quickly switch the load from the normalpower to the standby power under the controller control.Users can alsoposition the load in a neutral position if needed,disconnecting it from both thenormal and standby power supplies.This product is primarily used for Level 1and Level 2 loads as stipulated by the state,widely applicable in fireprotection,post and telecommunications,hospitals,hotels,urban rail transit,high-rise buildings,industrial assembly lines,television stations,and otherplaces requiring continuous power supply.Standby power supplies can be thegrid,self-starting generator sets,battery banks,etc.

Model Description

d5a672f1-7e04-4d22-b437-a08337ccf678

Notice:

The standard controller comes with grid-generator start-stop ports.Communication is optional.3N represents neutral line overlap transfer.

Working Environment

    □ Ambient air temperature: The ambient temperature ranges from-5℃ to +40℃,with an average temperature not exceeding+35℃ for 24 hours.Usersshould consult the manufacturer if the ambient air temperature exceeds+40℃ or falls below-5℃.
    □ The highest temperature of atmospheric humidity: At+40℃,the relative humidity does not exceed 50%,with a monthly maximum relative humidity of 90%.It toleratesthe effects of maritime damp air.Higher relative humidity is permissible atlower temperatures.Special measures should be taken for condensationoccasionally produced by temperature changes.
     Installation altitude: The installation site's altitude does not exceed 2000 meters.For higher altitudes,consider decreased dielectric strength andcooling effect of the air and consult the manufacturer.
    □ Pollution level: The environmental pollution level at the installation site is Level 3.
    □ Installation category: Installation Category IV.
    □ Installation inclination: The product is fixedly installed in the cabinet with a maximum inclination of±15°.
    □ Arcing distance: The arcing distance at AC400V is ≥60mm.

    Main Technical Parameters

      Model

      LMCT1-2000G

      Insulation voltage

      AC 1000V

      Rated voltage

      AC380V,AC400V,AC415V

      Rated current

      800A

      1250A

      2000A

      Rated impulse withstand voltage

      12kV

      Kind of throw

      Double throw

      Wiring method

      Behind horizontal wiring

      Short-time resistance current

      120kA

      Rated Control Power Current

      16A

      Transfer time

      A Power

      Input

      80ms

      80ms

      100ms

      Break

      30ms

      30ms

      30ms

      B Power

      Input

      100ms

      100ms

      120ms

      Break

      30ms

      30ms

      30ms

      Electrical Life

      3000

      3000

      Mechanical Life

      7000

      7000

      Use type

      AC-33B

      Accessaries

      Handle manual,electric conversion,controller automatic conversion



      Structure and Mounting Dimensions

                       bd886228-4a0a-4ff4-a29f-700f88a25ae959f30c9e-b311-43a2-bb82-9ec8a5b79cac  

                              5673fd99-5c58-4816-bc0a-94b0953f1453

                                             

      Leave Your Message