Rated Voltage: AC220V

,

Operating Frequency: 50Hz/60Hz

,

Voltage Measurement Accuracy: ± 1%

,

Frequency Measurement Accuracy: ± 0.05 Hz

,

Adjustable Switching Time: 0.5-30s

,

Communication Interface: RS485, Ethernet (optional)

,

Supported Communication Protocols: Modbus RTU, TCP/IP (optional)

,

Working Temperature Range: -10 °C to +60 °C

,

Working Environment Humidity: ≤90% Rh (no condensation)

,

For inquiries, please contact our expert team at sale@lvma-ele.com.

,

As a leading China supplier and factory, we pride ourselves on providing high-quality electrical products tailored to meet your needs. Our devices are designed for precision and reliability in various operating conditions.

    LMS1-LA Series Manual

    LMS1-LA as our ingenuity research and development of a new generation of dual power automatic transfer switch, in the performance and technology to achieve a major breakthrough. The product provides 63A, 125A, 250A, 400A, 630A and other rated current specifications, whether it is the continuous operation of massive servers in data centers, or the uninterrupted power supply of life support equipment in hospital ICU wards, the stable operation of elevator and fire fighting system in high-rise buildings can fully meet the power demand in different scenarios. ​

    Its switching speed can be called industry-leading, switching time only 10ms-50ms, with millisecond response speed to complete power conversion. In the data center, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time in the face of sudden power failure, avoiding data loss and system collapse caused by momentary power failure; in the hospital environment, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time, millisecond-level power switching can guarantee the stable operation of precision instruments and first-aid equipment in operating rooms, and escort the safety of patients. When applied to high-rise buildings, fast power changeover ensures smooth parking of elevators, normal operation of fire fighting systems and improved building Factor of safety. ​
    The transfer switch is composed of a high performance excitation contactor and an intelligent controller. When working, the electromagnetic coil produces a strong and stable attraction to drive the switching action to ensure the instant completion of power switching. This feature not only effectively guarantees the rapid switching of the power supply when the equipment is powered off, but also realizes the seamless connection of the power supply, which provides a reliable and solid power guarantee for the equipment with strict requirements for power continuity. ​

    The Dual Power Automatic Transfer Switch Controller is a dual power supply system for the design of intelligent control equipment, designed to ensure that in the complex and changeable power environment, load can be sustained, stable and reliable power supply. Through the comprehensive monitoring of the two power supplies, it can accurately judge the status of the power supply, and quickly switch the power supply according to the preset logic, which effectively solves the problem of power interruption caused by power failure, widely used in hospitals, data centers, financial institutions, industrial production and other areas of high demand for power supply continuity.
    Functional Characteristics
    Precise Power Supply Monitoring
    • Voltage Monitoring: Real-time, accurate measurement of two power supply voltage values, with configurable over-voltage and under-voltage thresholds (e.g., for 220V mains, accurately identifies >242V or <198V).
    • Frequency Monitoring: Strictly tracks power supply frequency to ensure stability within 50 Hz ± 0.5 Hz for frequency-sensitive equipment.
    • Phase Monitoring: Monitors the 120° phase difference in three-phase systems to timely detect excessive phase deviation or wrong phase order.
    Intelligent Switching Control
    • Automatic Switching: Rapidly switches load to standby power (within tens of milliseconds to seconds) upon detecting faults like over-voltage, under-voltage, phase loss, or abnormal frequency.
    • Manual Switching: Operators can flexibly switch power supplies via controller panel buttons or remote commands.
    • Flexible Switching Logic: Customizable priority settings for main and standby power. Adjust delay times between 0.5 to 5 seconds to avoid false triggers from temporary fluctuations.
    • Multiple Alarm Prompts: Immediate sound and light alarms for abnormalities, displaying specific fault types like over-voltage, under-voltage, phase lack, and frequency errors.
    • Communication Function: Select models feature RS485 and Ethernet interfaces for remote monitoring, operations, and data transmission.
    Main Technical Parameters
    Products Model Number Y-701 Y-702
    Installation method

    Fission type

    Display mode

    Indicator light

    LED

    Rated duty

    Uninterrupted duty

    Self-input and self restore

    Normal port and standby port share to each other

    Generator auto-start function

    Normal power detect

    Standby power detect

    Four-phase lacking phase detection, three-phase over-voltage/under-voltage detection

    Passive fire protection input

    Four-phase lacking phase detection, three-phase over-voltage/under-voltage detection

    (DC9-36V) active fire protection input

    Active fire control input

    Voltage real-time display

    Normal power and standby power indication

    Normal power and standby power

    Over-voltage/under-voltage adjustable

    ■ (F/F1)

    Generator rev. Stop time adjustable

    Programmable output

    RS485 communicating function

    Product Features

    Y-701/702 FUNCTION OF EACH TERMINAL

    R- R+ GND R1 485B (-) 485A (+) EGND
    □ R- & R+: DC9V-36V active fire control input enabled
    □ GND & R1: Short circuit, passive fire control unit enabled
    □ 485A & 485B: RS485 communication terminal, EGND: Frame Ground
    Communication Protocol Parameters:
    Local host: 1 (1-32, customizable) | Baud rate: 9600bps | Data bit: 8 | Parity bit: none | Stop bit: 1
    M3, M4: Standby power passive closing auxiliary output. Outputting time depends on ATS Model (approx. 3 seconds within magnet exciting coil, Electric type ATS can be more than 10 seconds).
    L2: Standby power active closing feedback input, limited to phase A/B/C.
    A2: Standby power phase A output, feedback to the closing standby power.
    A2, B2, C2, N2: Standby power three-phase & four-wire input.
    T1, T2: All off signal output (active or passive depending on ATS model). Equipped with PC class three sections ATS: 220AC active output; equipped with seclusion type ATS: passive.
    F2, F1, F: In Y-701 controller, F1 and F are starting generator signal outputs; in Y-702, F1 and F are programmable outputs.
    A1, B1, C1, N1: Normal power three-phase & four-wire input.
    A1: Phase A normal output, feedback to closing normal power.
    L1: Normal power active closing feedback input, limited to phase A/B/C.
    M1, M2: Normal power passive closing auxiliary output (outputting time refers to M3 & M4).
    Product Dimensions
    Frequently Asked Questions
    What is the primary function of the Dual Power Automatic Transfer Switch Controller?
    It is designed to monitor two power supplies in real-time, judge their status, and automatically switch the load to the standby power supply during power failures to ensure a continuous and stable power supply.
    What parameters does the controller monitor to detect power faults?
    The controller performs precise monitoring on voltage (detecting over-voltage and under-voltage), frequency (tracking stability within 50 Hz ± 0.5 Hz), and phase difference (detecting anomalies in three-phase systems like incorrect phase order).
    How fast does the controller switch power supplies?
    When a fault is detected in the main power supply, the controller automatically switches the load to the backup supply in a very short time, typically ranging from tens of milliseconds to seconds.
    What are the main differences between the Y-701 and Y-702 models?
    The Y-701 uses indicator lights for display and lacks RS485 communication. The Y-702 features an LED display, normal/standby power indication, programmable outputs, and RS485 communication capabilities.
    Can the controller interface with fire control systems?
    Yes, both models feature terminals for active fire control input (DC 9V-36V via R- & R+) and passive fire control unit enabling via GND & R1 short circuit.
    Is the switching delay adjustable?
    Yes, the controller has a customizable switching delay that can be adjusted within 0.5 to 5 seconds to prevent false switching caused by brief, temporary power fluctuations.