China LMS1-LA3 Series Automatic Transfer Switch ATS 630A - Reliable Suppliers and Factory Direct Solutions

,

Model Name: LMS1-LA3

,

Rated Working Voltage: AC230V, AC400V

,

Rated Working Current: 16A-630A

,

Pole: 2P, 3P, 4P

,

Rated Insulation Voltage: AC 690V

,

Frame Class: 63, 125, 250, 630

,

Rated Frequency: 50Hz

,

Product Category: PC Class

,

Features: 2 Position, Built-in ATS Controller

,

Drive Mode: Excitation Type

,

Certification: CE, CB, CCC

,

Standard: IEC 60947-6-1

,

Email: sale@lvma-ele.com

,

Overview: Discover the highly reliable LMS1-LA3 model, manufactured by leading suppliers in China. This advanced electrical device is designed for high performance, featuring a rated working voltage of AC230V and AC400V, making it suitable for various industrial applications. With a rated working current ranging from 16A to 630A and options for 2P, 3P, and 4P configurations, it meets diverse operational needs. The LMS1-LA3 is engineered under stringent quality standards, boasting a rated insulation voltage of AC 690V, and conforms to IEC 60947-6-1 regulations. Trust in a factory that upholds international certifications such as CE, CB, and CCC, ensuring your peace of mind. For more information, please contact us at sale@lvma-ele.com.

,
    LMS1-LA Series Manual

    LMS1-LA as our ingenuity research and development of a new generation of dual power automatic transfer switch, in the performance and technology to achieve a major breakthrough. The product provides 63A, 125A, 250A, 400A, 630A and other rated current specifications, whether it is the continuous operation of massive servers in data centers, or the uninterrupted power supply of life support equipment in hospital ICU wards, the stable operation of elevator and fire fighting system in high-rise buildings can fully meet the power demand in different scenarios. ​

    Its switching speed can be called industry-leading, switching time only 10ms-50ms, with millisecond response speed to complete power conversion. In the data center, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time in the face of sudden power failure, avoiding data loss and system collapse caused by momentary power failure; in the hospital environment, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time, millisecond-level power switching can guarantee the stable operation of precision instruments and first-aid equipment in operating rooms, and escort the safety of patients. When applied to high-rise buildings, fast power changeover ensures smooth parking of elevators, normal operation of fire fighting systems and improved building Factor of safety. ​
    The transfer switch is composed of a high performance excitation contactor and an intelligent controller. When working, the electromagnetic coil produces a strong and stable attraction to drive the switching action to ensure the instant completion of power switching. This feature not only effectively guarantees the rapid switching of the power supply when the equipment is powered off, but also realizes the seamless connection of the power supply, which provides a reliable and solid power guarantee for the equipment with strict requirements for power continuity. ​

    LMS1-LA3 is a PC-level dual power automatic transfer switch, the current specification covers 16A-630A, there are two types of 3p and 4p, the use of isolated switch type structure with motor drive body, for one two-stage design, with good electrical isolation performance, can ensure the safety and reliability when switching power supply.

    Model Description

    Model Description of LMS1-LA3

    Main Technical Parameters

    Model Name LMS1-63LA3 LMS1-125LA3 LMS1-250LA3 LMS1-630LA3
    Rated insulation voltage(Ui) AC 690V
    Rated working voltage(Ue) AC 400V
    Rated working current(Ie) 16~63A 20~125A 160~250A 315~630A
    Rated concussion withstand voltage(Uimp) 8kV
    Using category AC-33iB
    Kind of throw Double throw
    Wiring method Front board
    Poles 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P
    Performance Short-time resistance current 5kA 10kA 12.6kA
    Through to breaking capacity 10Ie 6Ie 6Ie
    Electrical Life / Mechanical Life 6000 / 20000 1000 / 4000
    Wiring Configuration Diagram
    • ✓
      Start generator: when fault occurs in the normal power, this port will connect after delaying some time.
    • ✓
      Normal close: When the normal power of ATS is in closing state, closing signal without power is output from this port.
    • ✓
      Standby close: When the standby power of ATS is in closing state, closing signal without power is output from this port.
    • ✓
      Normal earth wire: When ATS are 3 phases, the normal earth wire is connected into this port.
    • ✓
      Standby earth wire: When ATS are 3 phases, the standby earth wire is. Remark: The normal earth wire and standby earth wire is just suitable for ATS of 3 phases.

    Communication port description

    • ⚙
      485A and 485B: RS485 communication terminal
    • ⚙
      Communication protocol parameters, module address: 1 (range: 1-32, user can set)
    • ⚙
      Baud rate: 9600bps
    • ⚙
      Data bits: 8 bits
    • ⚙
      Parity bit: none
    • !
      Note: NC is reserved for undefined ports, users are not allowed to connect

    Structure and Mounting Dimensions

    LMS1-LA3 Series PC Automatic transfer switch Ats 604
    Dimensions drawing 1
    Dimensions drawing 2
    FAQ
    What is the current range specification for the LMS1-LA3 ATS?
    The LMS1-LA3 automatic transfer switch series covers current specifications ranging from 16A up to 630A.
    What pole configurations are available for the LMS1-LA3?
    The LMS1-LA3 dual power automatic transfer switch is available in both 3P (three-pole) and 4P (four-pole) configurations.
    Does the LMS1-LA3 ATS support remote communication?
    Yes, it features RS485 communication terminals (485A and 485B) supporting Modbus protocol parameters with a default baud rate of 9600bps and an adjustable module address range from 1 to 32.
    What is the electrical and mechanical lifespan of the switch?
    For the LMS1-63LA3 model, the electrical life is rated at 6,000 cycles, and the mechanical life is rated at 20,000 cycles. For the larger LMS1-630LA3 model, it is rated at 1,000 electrical cycles and 4,000 mechanical cycles.
    How does the generator startup port function during a power failure?
    When a fault is detected in the normal power supply, the "Start generator" port will close and connect after a set delay time to automatically start the standby generator.