China LMS1-LA3 Series 630A Automatic Transfer Switch ATS - Reliable Suppliers & Factory Solutions

,

Model Name: LMS1-LA3

,

Rated Working Voltage: AC230V, AC400V

,

Rated Working Current: 16A-630A

,

Pole Configuration: 2P, 3P, 4P

,

Rated Insulation Voltage: AC 690V

,

Frame Class: 63, 125, 250, 630

,

Rated Frequency: 50Hz

,

Product Category: PC Class

,

Key Features: 2 Position, Built-in ATS Controller

,

Drive Mode: Excitation Type

,

Certifications: CE, CB, CCC

,

Standards Compliance: IEC 60947-6-1

,

Contact Email: sale@lvma-ele.com

,

Discover the LMS1-LA3, a top-quality product manufactured by trusted China suppliers and factories. This versatile device is designed to operate at rated voltages of AC230V and AC400V, with a working current range of 16A to 630A. Available in various pole configurations (2P, 3P, 4P), the LMS1-LA3 meets rigorous standards and provides exceptional reliability. With a rated insulation voltage of AC 690V and adherence to IEC 60947-6-1 standards, it is perfect for various industrial applications. Explore the advanced features such as the built-in ATS controller and choose the LMS1-LA3 for your electrical solutions.

,
    LMS1-LA Series Manual

    LMS1-LA as our ingenuity research and development of a new generation of dual power automatic transfer switch, in the performance and technology to achieve a major breakthrough. The product provides 63A, 125A, 250A, 400A, 630A and other rated current specifications, whether it is the continuous operation of massive servers in data centers, or the uninterrupted power supply of life support equipment in hospital ICU wards, the stable operation of elevator and fire fighting system in high-rise buildings can fully meet the power demand in different scenarios. ​

    Its switching speed can be called industry-leading, switching time only 10ms-50ms, with millisecond response speed to complete power conversion. In the data center, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time in the face of sudden power failure, avoiding data loss and system collapse caused by momentary power failure; in the hospital environment, the LMS1-LA automatic transfer switch can switch to the standby power supply in a very short period of time, millisecond-level power switching can guarantee the stable operation of precision instruments and first-aid equipment in operating rooms, and escort the safety of patients. When applied to high-rise buildings, fast power changeover ensures smooth parking of elevators, normal operation of fire fighting systems and improved building Factor of safety. ​
    The transfer switch is composed of a high performance excitation contactor and an intelligent controller. When working, the electromagnetic coil produces a strong and stable attraction to drive the switching action to ensure the instant completion of power switching. This feature not only effectively guarantees the rapid switching of the power supply when the equipment is powered off, but also realizes the seamless connection of the power supply, which provides a reliable and solid power guarantee for the equipment with strict requirements for power continuity. ​

    LMS1-LA3 is a PC-level dual power automatic transfer switch, the current specification covers 16A–630A, there are two types of 3P and 4P, the use of isolated switch type structure with motor drive body, for one two-stage design, with good electrical isolation performance, can ensure the safety and reliability when switching power supply.
    Model Description
    LMS1-LA3 Model Description
    Main Technical Parameters

    Model Name

    LMS1-63LA3

    LMS1-125LA3

    LMS1-250LA3

    LMS1-630LA3

    Rated insulation voltage (Ui)

    AC 690V

    Rated working voltage (Ue)

    AC 400V

    Rated working current (Ie)

    16~63A

    20~125A

    160~250A

    315~630A

    Rated concussion withstand voltage (Uimp)

    8kV

    Using category

    AC-33iB

    Kind of throw

    Double throw

    Wiring method

    Front board

    Poles

    2P

    3P

    4P

    2P

    3P

    4P

    2P

    3P

    4P

    2P

    3P

    4P

    Performance

    Short-time resistance current

    5kA

    10kA

    12.6kA

    Through to breaking capacity

    10Ie

    6Ie

    6Ie

    Electrical Life / Mechanical Life

    6000 / 20000

    1000 / 4000

    LMS1-LA3 Signal Port Diagram
    • Start generator: When fault occurs in the normal power, this port will connect after delaying some time.
    • Normal close: When the normal power of ATS is in closing state, closing signal without power is output from this port.
    • Standby close: When the standby power of ATS is in closing state, closing signal without power is output from this port.
    • Normal earth wire: When ATS are 3 phases, the normal earth wire is connected into this port.
    • Standby earth wire: When ATS are 3 phases, the standby earth wire is connected into this port. Remark: The normal earth wire and standby earth wire is just suitable for ATS of 3 phases.
    Communication Port Description
    • 485A and 485B: RS485 communication terminal
    • Communication protocol parameters, module address: 1 (range: 1–32, user can set)
    • Baud rate: 9600bps
    • Data bits: 8 bits
    • Parity bit: None
    ⚠ Note: NC is reserved for undefined ports. Users are not allowed to connect.
    Structure and Mounting Dimensions
    LMS1-LA3 Series PC Automatic Transfer Switch ATS 604LMS1-LA3 Mounting DimensionsAutomatic Transfer Switch Structure
    ❓ Frequently Asked Questions (FAQ)
    Q What is the current range covered by the LMS1-LA3 automatic transfer switch?
    The LMS1-LA3 series covers a current specification range of 16A to 630A, including models LMS1-63LA3 (16–63A), LMS1-125LA3 (20–125A), LMS1-250LA3 (160–250A), and LMS1-630LA3 (315–630A).
    Q What pole configurations are available for the LMS1-LA3?
    The LMS1-LA3 is available in 2P, 3P, and 4P configurations to suit various installation requirements and load types.
    Q What is the rated working voltage and insulation voltage of the LMS1-LA3?
    The rated working voltage (Ue) is AC 400V, and the rated insulation voltage (Ui) is AC 690V, making it suitable for standard industrial and commercial power systems.
    Q Does the LMS1-LA3 support RS485 communication?
    Yes, the LMS1-LA3 is equipped with RS485 communication terminals (485A and 485B). The default module address is 1 (range: 1–32, user-configurable), with a baud rate of 9600bps, 8 data bits, and no parity bit.
    Q What is the electrical and mechanical life of the LMS1-LA3?
    For models LMS1-63LA3, LMS1-125LA3, and LMS1-250LA3, the electrical life is 6,000 operations and the mechanical life is 20,000 operations. For the LMS1-630LA3, the electrical life is 1,000 operations and the mechanical life is 4,000 operations.
    Q How does the LMS1-LA3 ensure safe power switching?
    The LMS1-LA3 uses an isolated switch type structure with a motor-driven body and a one two-stage design. This provides excellent electrical isolation performance, ensuring safe and reliable power source switching between normal and standby supplies.